$139.97each
Description
Gas Ignition Control Board – replacement for Carrier LH33WP003/3A control boards
Specifications:
- Control Voltage: 24 VAC (18-30 VAC), 60Hz
- Line Voltage: 208/230 VAC, 60Hz
Timing:
- Pre-Purge: 45 seconds
- Trial for Ignition: 5+2 seconds
- Retry Period: Every 20 seconds for 15 minutes
- Lockout: Manual reset
- Post-Purge: 45 seconds
LED Indicators:
- Red LED: Steady ON-normal operation.
Flashing-fault codes Inputs:
- Power: RT and C
- Thermostat Interface: R,W, and G
- Safety Switches: RS, LS, and CS
- Combustion Motor Hall Effect Sensor
Flame Sensing Outputs:
- Spark – Gas Valve: GV
- Combustion Motor: CM
- Blower Motor: BM
- Indoor Fan Motor: IFO
MANUALS (2)
4 in stock
Fast Shipping
Carrier information
20k products
Payment methods
24/7 Support
Unlimited help desk
2-day Delivery
Track or off orders
Product Highlights |
Ignition Type: Intermittent Pilot |
---|---|
Specs |
Ignition Type: Intermittent Pilot ,Control Voltage: 18-30 VAC ,Operating Temp Range: -40° to 165°F ,Relative Humidity: 5% to 95% R.H. (non condensing) ,Trial For Ignition: 15 or 90 Seconds (switch selectable) |
Brand |
ICM Controls |
Description
Related products
Eaton Freedom NEMA Pneumatic Timer, 1-30 Sec, 1NO/1NC, Top Mount
In stock
FS1500L Frost Sentry Garage Thermostat (Horizontal)
In stock
Product Highlights |
Stages: 1 Heat ,Voltage: 24 VAC (18/30 VAC) ,Amperage: 1 amp max. per terminal, 2 amp max. total load Amps ,Power Method: Battery ,Mount: Horizontal ,Size: 3.75" |
---|---|
Specs |
Product Type: Garage Thermostat ,Application: Heating ,Stages: 1 Heat ,Voltage: 24 VAC (18/30 VAC) ,Amperage: 1 amp max. per terminal – 2 amp max. total load ,Temperature Control Range: 35°F to 75°F ,Accuracy: +/- 1°F ,Power Method: Battery ,Mount: Horizontal ,Height: 3.75" ,Width: 4.59" ,Depth (Inches): 1.12" |
Brand |
ICM Controls |
ICM401 Phase Loss and Reversal Protection, 190-600 VAC
In stock
Reviews
Clear filtersThere are no reviews yet.