$305.61each
Description
The CDE Series provides a user-selectable 4 to 20 mA or 0 to 10 Vdc output for versatility. Microprocessor-based digital electronics and a unique self-calibration algorithm improves long-term stability and accuracy.
Product Applications
- Controlling ventilation in response to occupancy
- Facilitating compliance with ASHRAE 62.1 standard for air quality
- Office buildings, conference rooms, schools, retail stores, etc.
Product Specifications
- Input Power: Class 2; 20 to 30 Vdc/24 AC 50/60 Hz; 100 mA max.
- Analog Output: 4 to 20 mA (clipped & capped)/0 to 10 Vdc (selectable)
- Operating Temp. Range: 0 to 50 °C (32 to 122 °F)
- Operating Humidity Range: 0 to 95% RH non-condensing
- Housing Material: High impact ABS plastic
- Terminal Block Torque (CDE): 0.5 to 0.6 N-m (4.4 to 5.3 in-lbf) max.
- Terminal Block Wire Size (CDE): 24 to 12 AWG (0.25 to 2.5mm2)
- Sensor Type: Non-dispersive infrared, diffusion sampling
- Output Range: 0 to 2000 ppm
- Accuracy: ±30 ppm ±2% of measured value
- Repeatability: ±20 ppm ±1% of measured value
- Response Time: <60 seconds for 90% step change
- Limited Warranty: 3 years
MANUALS (2)
4 in stock
Fast Shipping
Carrier information
20k products
Payment methods
24/7 Support
Unlimited help desk
2-day Delivery
Track or off orders
Product Highlights |
Mount: Duct ,Voltage: 24 VAC – 20-30 VDC ,Warranty: 3 Year Limited Warranty |
---|---|
Specs |
Sensor Type: CO2 – Non-dispersive infrared (NDIR) ,Mount: Duct ,Voltage: 24 VAC – 20-30 VDC ,Power Supply: Class 2 ,Control Signal: 0 to 10 VDC – 4 to 20 mA ,Operating Humidity: 0 to 95% RH (Non-Condensing) ,Housing Material: ABS Plastic ,Range: 0-2000 ppm ,Accuracy: ±30 ppm ±2% of reading ,Warranty: 3 Year Limited |
Brand |
Veris |
Description
Related products
ICM104 Delay on Make Timer (10-1,000 Second Knob Adjust. Delay)
In stock
ICM203F Delay on Break Timer, 6″ Wire Leads (.03-10 Minute Knob Adjust. Delay)
In stock
Product Highlights |
Voltage : 18/240 VAC ,Amperage : 1.5 Amps ,Size : 2" x 2" |
---|---|
Specs |
Product Type: Delay on Break ,Time Delay: 03-10 Min Knob Adjustable ,Wiring: 6" Wire Leads – 2 Wire ,Voltage: 18/240 VAC ,Amperage: 1.5 ,Amp Inrush: 15 ,Frequency: 50-60 Hz ,Voltage Drop: 3.5 V typical – 4.5 V maximum @ 1.5amps ,Holding Current: 40 mA (minimum) ,Size: 2" x 2" ,Replaces: TD73W – ADB-2 ,OEM: Supco – Wagner/DiversiTech |
Brand |
ICM Controls |
ICM493 Line Voltage, Single Phase Motor Protection w/ Surge Protection, 60A contactor
In stock
Reviews
Clear filtersThere are no reviews yet.